Series 101-A Electric Water Feeders

McDonnell & Miller : Water Feeders :

Features and Benefits

  • • For low pressure steam boilers with cold water feed
  • • Eliminates necessity to manually add water to the boiler
  • • Can be used with mechanical or electronic low water
  • cut-off controls
  • • Quick-change replaceable cartridge valve and strainer
  • Manual feed button
  • Model 101-A features a 120 VAC solenoid
  • Model 101-A-24 features a 24 VAC solenoid and a
  • separate 50VA transformer
  • Maximum water supply pressure 150 psi (10.5 kg/cm2)
  • Maximum boiler pressure 25 psi (1.8 kg/cm2)
  • Maximum inlet water temperature 120°F (49°C)
  • Maximum power consumption
  • – 40 VA at 24 VAC
  • – 40 VA at 120 VAC